Wire size for 200 amp service (2026): copper and aluminum, overhead and underground

Correct wire size for a 200 amp residential service: 2/0 copper or 4/0 aluminum (NEC 310.12), underground vs overhead, service entrance vs feeder, 2026 material cost.

Cost: $3–$12 per foot (service entrance wire)Time: N/A (planning)Difficulty: Hard — electrician work
By Ken Hoven · Published · Updated

The NEC-compliant wire size for a 200-amp residential service entrance is 2/0 AWG copper or 4/0 AWG aluminum under the dwelling-unit service rule in NEC 310.12. That rule applies to the service conductors feeding a single-family dwelling only. Feeders to subpanels, commercial services, and parallel runs use the standard ampacity tables and run larger. Here's the full breakdown with ampacities, cable types, and what it costs in 2026.

Quick answer

Application Copper Aluminum / aluminum alloy
200A residential service entrance (dwelling unit, NEC 310.12) 2/0 AWG 4/0 AWG
200A feeder in a home with a 200A service (NEC 310.12(B) and (C)) 2/0 AWG 4/0 AWG
200A feeder carrying only part of the load from a larger service, such as 400A (NEC 310.16, 75°C) 3/0 AWG 250 kcmil
200A service entrance on a non-dwelling (NEC 310.16, 75°C) 3/0 AWG 250 kcmil
Grounded (neutral) conductor on a 200A residential service 2/0 AWG copper or 4/0 AWG aluminum (same as ungrounded, when carrying full neutral load) —
Grounding electrode conductor (ground to rod/pipe) 4 AWG copper 2 AWG aluminum

For a typical 200-amp residential service, the common installed wire is 4/0-4/0-4/0-2/0 aluminum SER or XHHW (three 4/0 and one 2/0 for the ground), or 2/0-2/0-2/0-4 copper SER when copper is specified.

Why the dwelling rule gives you smaller wire

NEC 310.12 allows reduced conductor sizes for 120/240V single-phase dwelling-unit services and feeders because residential load diversity means the service rarely runs at nameplate capacity. The 2/0 copper or 4/0 aluminum sized for 200A is based on this diversity allowance and is specific to the service entrance or the feeder serving the main dwelling disconnect. It does not apply to:

  • A 200A feeder that carries only part of the dwelling's load off a larger service (a 200A subpanel fed from a 400A service, for example). The one allowance, in 310.12(C), is that no feeder in a dwelling has to be larger than its service conductors
  • Feeders to detached garages, outbuildings, or ADUs billed as separate loads
  • Commercial services and the service to a two-family or multifamily building (use NEC 310.16)
  • Parallel conductor installations

For those, size per the standard 75°C ampacity table (310.16), which puts 200A at 3/0 copper or 250 kcmil aluminum.

Overhead vs. underground

The wire size itself is the same for overhead and underground installations, but the cable type changes.

Overhead service drop (utility to weatherhead, typically the utility's responsibility to the point of attachment):

  • Service-drop cable is usually triplex or quadruplex aluminum (two or three insulated conductors wrapped around a bare messenger).
  • Common sizes: 4/0-4/0-2/0 Aluminum Triplex for 200A service drops.
  • From the weatherhead to the meter, SE (Service Entrance) cable — typically SEU for overhead applications.

Underground service lateral (meter to the panel, or utility to meter if underground):

  • USE or USE-2 aluminum rated for direct burial, or XHHW/XHHW-2 in conduit.
  • 4/0-4/0-4/0-2/0 aluminum is the typical 200A underground service.
  • If run in conduit, the conduit size matters — 2" PVC is common for a 200A aluminum service.

Burial depth (NEC Table 300.5, measured to the top of the cable or conduit): 24" minimum for direct-burial USE; 18" in PVC conduit; 6" in rigid metal or intermediate metal conduit. Utilities often require more for the service lateral, and their rule wins.

Service entrance vs. feeder (same wire, different name)

Service entrance conductors: from the utility connection (weatherhead or meter base) to the service disconnect (main breaker). Typically SE, SEU, SER, or individual USE/XHHW conductors in conduit.

Feeders: from the main service disconnect to a subpanel. Same sizing rule (2/0 copper or 4/0 aluminum for a 200A dwelling-unit feeder), but typically SER cable (has the insulated grounded conductor plus a separate insulated or bare equipment grounding conductor) — the 4-wire version required by NEC 250.32 when the subpanel is in a separate structure or on the same structure as the service.

The service entrance uses 3-wire (two hots and a neutral); the feeder uses 4-wire (two hots, neutral, and separate ground).

2026 material cost

Prices vary by metal commodity price and region; 2026 approximations:

Cable Typical 2026 price per foot
4/0-4/0-4/0-2/0 aluminum SER (200A feeder) $5–$9/ft
4/0-4/0-2/0 aluminum SEU (200A service entrance) $4–$7/ft
2/0-2/0-2/0-4 copper SER (200A feeder) $10–$18/ft
2/0-2/0-2/0 copper SEU (200A service entrance) $8–$14/ft
4/0 aluminum USE (direct bury, each conductor) $1.50–$3/ft
2/0 aluminum USE (each conductor) $1–$2/ft

A typical 40-foot aluminum service entrance runs $160–$360 in wire alone. The copper equivalent runs $320–$720. Copper vs. aluminum on a 200A service adds $5–$15/ft — most residential installs use aluminum for cost reasons, and it is fully Code-compliant with proper anti-oxidant compound at terminations.

Copper or aluminum?

Aluminum is the standard choice for 200A service conductors and has been for decades. Aluminum service entrance wire has an excellent track record when terminated correctly (anti-oxidant compound, torqued to spec, approved lugs). The problems with aluminum branch circuit wiring from the 1960s–70s are a different animal — that was 15A/20A solid aluminum on brass terminals, not stranded aluminum service wire on aluminum-rated lugs.

Reasons to spec copper on a 200A service:

  • You're in a jurisdiction that requires it (uncommon for residential)
  • You want the smaller wire diameter (2/0 copper vs. 4/0 aluminum) to fit a tight conduit run
  • Personal preference and willing to pay the ~2× premium

Both are correct. Most modern residential installs are aluminum.

Grounding electrode conductor

Separate from the service conductors. For a 200A residential service, NEC Table 250.66 gives you:

  • 4 AWG copper (or 2 AWG aluminum) for a 2/0 copper or 4/0 aluminum service, which covers the run to a metal water pipe
  • 6 AWG copper is all that is required for the portion that runs only to a ground rod (NEC 250.66(A)), and 4 AWG copper is the most required to a concrete-encased (Ufer) electrode (250.66(B))
  • A second ground rod is required unless a single rod tests at 25 ohms or less (NEC 250.53(A)(2)); most installers simply drive two

The grounding electrode conductor is sized to the service entrance conductor, not to the load — a bigger service means a bigger grounding electrode conductor.

Conduit size

If you're running the service entrance in conduit:

  • 4/0 aluminum (3 conductors + 2/0 neutral) fits in 2" rigid or EMT per NEC Chapter 9 fill tables
  • 2/0 copper (3 conductors + 4 neutral) fits in 1-1/4" or 1-1/2" rigid depending on conductor count

Local utility rules often specify minimum conduit size independent of fill — check the utility's electric service handbook before you buy pipe.

Not DIY

Service entrance work is licensed-electrician-and-utility-coordination work in every U.S. jurisdiction. The service conductors terminate in lugs that are energized from the utility side; the only way to work on them safely is to have the utility pull the meter and kill the service. That's not a homeowner task.

Homeowners planning a service upgrade or panel replacement benefit from understanding wire sizes for one reason: to read the quote and spot problems. If a 200A service quote lists 4 AWG aluminum, something is very wrong. If it lists 4/0 aluminum, you're in the right territory.

Common questions

What size wire do I need for a 200 amp service?

For a single-family residential 200A service under NEC 310.12, 2/0 AWG copper or 4/0 AWG aluminum. Most installs use 4/0 aluminum because it's about half the cost of equivalent copper and fully code-compliant when terminated properly.

Can I use 2/0 aluminum for a 200 amp service?

No. The aluminum size for a 200A dwelling service is 4/0, not 2/0. Under the dwelling rule, 2/0 aluminum is the size for a 150A service; its table ampacity at 75°C is 135A. Neither is enough for 200A.

What size is the neutral on a 200 amp service?

In a single-phase 120/240V residential service, the neutral is typically the same size as the ungrounded conductors (2/0 copper or 4/0 aluminum) when expected to carry full neutral load. NEC 220.61 allows the neutral to be sized smaller based on calculated neutral load, which is why you'll sometimes see 2/0 aluminum as the neutral in a 4/0 aluminum service — Code-compliant when the load calc supports it.

How deep do I bury 200 amp service wire?

NEC Table 300.5: 24 inches minimum for direct-burial USE; 18 inches in PVC conduit; 6 inches in rigid metal conduit. Local utility rules for the service lateral are often deeper.

What's the difference between SE, SER, SEU, and USE?

SE = Service Entrance cable (generic). SEU = SE cable with concentric neutral and no separate ground, used for overhead service drops. SER = SE Round, 4-wire (two hots, neutral, ground) used for subpanel feeders. USE = Underground Service Entrance, suitable for direct burial, one insulated conductor per run.

How much does 200 amp service wire cost?

In 2026, aluminum SER (4/0-4/0-4/0-2/0) runs $5–$9/ft; copper SER (2/0-2/0-2/0-4) runs $10–$18/ft. A typical 40-foot service entrance costs $160–$720 in wire depending on metal and configuration. This is a fraction of total service upgrade cost ($1,500–$4,000), which is dominated by labor, panel, and utility coordination. See our 100 amp vs 200 amp panel guide for the full upgrade cost.

About these numbers: cost ranges are typical 2026 U.S. planning figures compiled from published cost guides and retailer pricing. They are not quotes. Verify prices locally, and use a licensed professional for electrical, gas, roofing, structural, and permit-required work.